Earth Fault Loop Impedance (Zs)
Verify earth-fault loop impedance Zs against the BS 7671 maximum for the protective device.
The Ensign ToolboxEarth Fault Loop Impedance (Zs)Verify earth-fault loop impedance Zs against the BS 7671 maximum for the protective device.
Supply (origin)
Ω
0.35 Ω TN-C-S (PME) max; 0.8 Ω TN-S max; or a measured value
Circuit conductors
mΩ/m
Combined line + cpc resistance per metre
Copper T&E line/cpc pairs at 20 °C. Verify against actual cable data.
m
Protective device
Ω
Tabulated value already includes Cmin = 0.95
BS EN 60898 / 61009 MCBs at 230 V, 0.4 s. Verify the disconnection time required.
× max
0.8 (80 %) rule — a COLD site-measured Zs should be below this
Enter Ze, (R1+R2)/m and length to calculate