Earthing & Bonding Conductor Sizing

Size the earthing conductor (Table 54.7 or adiabatic), main protective bonding (Table 54.8 / PME) and supplementary bonding to BS 7671.

Supply

PME main bonding sizes from the supply neutral (Table 54.8); TN-S / TT from the earthing conductor

mm²

Copper-equivalent csa — confirm with the DNO

Earthing conductor

mm²

Keys Table 54.7: S ≤ 16 → S; 16 < S ≤ 35 → 16; S > 35 → S/2

Supplementary bonding

mm²

The smaller CPC when connecting two exposed-conductive-parts

Enter the line conductor and CPC csa to size the conductors