Hot Water Secondary Return Sizing

Size a DHW secondary return circuit (CIBSE Guide G): array-first circuit heat loss, return flow to hold the design ΔT, pipe size and bronze pump duty, plus a dead-leg advisory.

Circuit segments

No segments added yet — add each straight run of the secondary return circuit

Design temperatures

°C

HSE: store DHW ≥60°C

K

Return flow ṁ = Q ÷ (cp × ΔT); default 5 K — editable, see engine notes

°C

≥50°C general, 55°C healthcare (HSE / CIBSE Journal Module 87)

Insulation & ambient (shared across segments)

°C

Return pipe & limits

m/s

CIPHE Design Guide Table 17: circulation areas ≤1.5 m/s (noise)

Pa/m

CIBSE Guide B1 life-cycle criterion (≤200 Pa/m)

kg/m³

Default at 60°C (thermexcel.com); adjust if flow temp differs materially

Pa·s

Bronze pump duty

m
m head
%

Typical 5–15% on total head

%

Small bronze wet-rotor circulators typically 20–40%; larger end-suction 50–65%

m/s²

Dead-leg advisory

m
mm

Default = 15 mm copper internal bore

Add at least one circuit segment (length, OD, insulation) to size the return